What the standard asks for, how often to clean, and the records your insurer and fire risk assessor expect.
If you run a commercial kitchen in Leeds, West Yorkshire, York or Harrogate, the standard your extract system is judged against is TR19 Grease. This guide explains what it asks for, how often a kitchen needs cleaning, and what paperwork you should have.
Page reviewed 30 September 2026 by Leeds Canopy Cleaning, a quote-arranging service. The cleaning is carried out by an independent specialist provider.
TR19 Grease is a specification published by BESA in 2019 for managing the fire risk from grease in kitchen extract systems. It replaced the grease section of the older TR19 document, which now covers general ventilation hygiene. It sets out how often systems should be cleaned, how clean is clean enough, how the work should be done and what the post-clean report should contain.
| Daily cooking | Usage band | Minimum clean | Typical Leeds kitchens |
|---|---|---|---|
| 12โ16 hours | Heavy | Every 3 months | Takeaways, curry houses, chip shops, city-centre restaurants open all day |
| 6โ12 hours | Moderate | Every 6 months | Most restaurants, pub kitchens, hotel kitchens |
| 2โ6 hours | Light | Every 12 months | Cafรฉs, school kitchens, small care home kitchens |
These are minimums. The real interval should come from the grease readings taken at each clean, the type of cooking and how the menu changes through the year. West Yorkshire Fire and Rescue Service recommends servicing every three to six months depending on usage.
TR19 Grease sets a limit of a mean 200 microns of grease across the system between cleans โ roughly half the thickness of a business card. Any reading of 500 microns or more needs an immediate spot clean. Deposits are measured with a wet film thickness test or a deposit thickness test before and after the clean, so the certificate proves the result.
The whole extraction route: canopies, filters, plenums, risers, horizontal ductwork, the extract fan and the discharge point. Access panels are fitted at regular intervals โ typically every two to three metres where the layout allows โ so every section can be reached. A canopy-only clean does not meet the standard. See TR19 extract cleaning, ductwork cleaning and fan cleaning.
You should receive before-and-after photographs from matching positions, the grease test results, a written summary including any areas that could not be reached, and a hygiene certificate with the date, the location and the name of the technician. Keep it with your fire risk assessment โ it is the first thing a loss adjuster asks for after a fire.
West Yorkshire Fire and Rescue Service says around 70% of fires in pubs, restaurants and takeaways are caused by dirt and grease building up in extractor and ventilation systems (WYFRS, February 2023). In July 2023 a fire on North Street in Keighley that was believed to have started when flames from a cooker spread to an extractor flue went on to reach the flats above a takeaway (WYFRS incident report). In Harrogate in 2014, a fire in the kitchen extraction ducting of a restaurant on Albert Street spread through the ducting to other floors and destroyed the roof.
The Regulatory Reform (Fire Safety) Order 2005 requires the responsible person to assess and reduce fire risk, and kitchen extract belongs in that assessment. Most commercial kitchen insurance policies also carry a condition that the extract is cleaned to a recognised standard. Without the certificates, a claim after a grease fire can be reduced or refused.
Council food safety officers score the condition and cleanliness of the premises, and a greasy canopy and dripping filters count against you. In England you do not have to display your food hygiene rating sticker, but customers can look it up online and on delivery apps.
There is no law that names TR19, but the Regulatory Reform (Fire Safety) Order 2005 requires the responsible person for a business premises to assess and reduce fire risk, and a grease-laden extract is a recognised fire risk. TR19 Grease is the standard insurers and fire risk assessors use to judge whether that risk is being managed.
Minimums are set by daily cooking hours: every three months for 12 to 16 hours a day, every six months for 6 to 12 hours, every twelve months for 2 to 6 hours. The actual interval should follow the grease readings, so a heavy-frying kitchen can need cleaning more often.
TR19 Grease sets a mean limit of 200 microns across the system between cleans. Any reading of 500 microns or more calls for an immediate spot clean.
No. Filters should be cleaned daily or as the manufacturer instructs, but no filter stops all the grease. The canopy, ductwork and fan still need a professional clean.
Fire safety in West Yorkshire falls under West Yorkshire Fire and Rescue Service, and in York and Harrogate under North Yorkshire Fire and Rescue Service. Food hygiene is inspected by the local council, such as Leeds City Council. Your insurer will also ask for certificates after any claim.